Mitsubishi Electric MELIPC MI5000 Series User Manual page 34

Startup
Hide thumbs Also See for MELIPC MI5000 Series:
Table of Contents

Advertisement

Power Supply Wiring Precautions
The following shows the considerations when wiring the power supply of this product.
■Wiring of power supply, I/O power supply wiring, and motor wiring
Wire cables of the product power supply, I/O power supply, and motor power supply separately as shown below.
Main
power supply
100VAC
200VAC
Relay
terminal
block
■If high noise
Use an isolation transformer to reduce the noise such as the lightning surge.
Product name
Isolation transformer
■Installation of breaker or external fuse
Considering the rated current and inrush current of the power supply module, install a breaker having the appropriate sensing
property or an external fuse causing proper blowout.
When a single product is used, connecting a breaker around 10 A or an external fuse is recommended in order to protect the
power source.
■Power supply wiring
Do not install 100 VAC or 24 VDC wires bundled with or near the main circuit lines (high voltage and large current) or I/O
signal wires (including common lines). Keep a distance of 100 mm or more from these lines.
2 PRODUCT INSTALLATION
32
2.3 Wiring the Power Supply Module
MELIPC power
Isolation
supply
transformer
T1
I/O power supply
Motor power supply
Model name
Manufacturer
4H503-345
Mitsubishi Electric System & Service, Co., Ltd.
MELIPC
I/O equipment
Motor
equipment

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melipc mi5122-vw

Table of Contents