Appendix 13Emc And Low Voltage Directives; Measures To Comply With The Emc Directive - Mitsubishi Electric MELIPC MI5000 Series User Manual

Startup
Hide thumbs Also See for MELIPC MI5000 Series:
Table of Contents

Advertisement

Appendix 13
Compliance with the EMC Directive, which is one of the EU directives, has been mandatory for products sold within EU
member states since 1996, as has compliance with the Low Voltage Directive since 1997, also a EU directive.
For products compliant to the EMC and Low Voltage Directives, their manufacturers are required to declare compliance and
affix the CE marking.
The sales representative in EU member states is:
Company: MITSUBISHI ELECTRIC EUROPE B.V.
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany

Measures to comply with the EMC Directive

The EMC Directive sets requirements for emission (conducted and radiated electromagnetic interference emitted by a
product) and immunity (the ability of a product not to be influenced by externally generated electromagnetic interference).
This section describes the precautions for machinery constructed with this product, to comply with the EMC Directive.
These precautions are based on the requirements of the EMC Directive and the harmonized standards. However, they do not
guarantee that the entire machinery constructed according to the descriptions complies with the EMC Directive.
The manufacturer of the machinery must determine the testing method for compliance and declare conformity to the EMC
Directive.
Cable processing
■Ethernet cable, CC-Link IE Field Network cable
For twisted pair cables connecting to 10BASE-T/100BASE-TX/1000BASE-T connectors and CC-Link IE Field Network
connectors, use shielded twisted pair cables. Additionally, ensure that the shielded part of the twisted cables is grounded.
■RS-232 cable
Additionally, for the RS-232 cables, ensure that the shielded part of the twisted cables is grounded.
■USB cable, DisplayPort cable
Use shielded cables. Additionally, ensure that the DisplayPort cable is 3 m or less in length.
■I/O connector
Use shielded cables, and ensure that the shielded part is grounded. Furthermore, use a cable with a length of 30 m or less.
EMC Directive related standards
■Emission requirements
Standard: EN61131-2:2007
Test item
CISPR16-2-3
*1
Radiated emission
CISPR16-2-1, CISPR16-1-2
*1
Conducted emission
*1 This product is an open-type device and must be placed in a conductive control panel or similar type of enclosure. The tests were
conducted with the product installed in a control panel, applying the maximum rated input voltage of the power supply module.
*2 QP: Quasi-Peak value, Mean: Average value
APPX
174
Appendix 13 EMC and Low Voltage Directives
EMC and Low Voltage Directives
Test description
The electromagnetic wave emitted by the product
to the external space is measured.
The noise level which the product emits to the
power line is measured.
Value specified in standard
• 30 to 230 MHzQP: 40 dBμV/m (measured at 10
*2
m distance)
• 230 to 1000 MHzQP: 47 dBμV/m (measured at
10 m distance)
• 150k~500kHzQP: 79dB, Mean: 66dB
• 500k~30MHzQP: 73dB, Mean: 60dB
*2

Advertisement