3.1 Overview of Settings

3.1.1 System Example

This chapter describes the case of setting FP0H(A) in the following system example.
Originator
Target
Originator
Target
: Opens connection.
Operation of FP0H(A)
• The data received from the Tag (Tag_Test2) of the FP0H(B) is stored in the data area
(LD40 to 49) of the FP0H(A). The FP0H(A) is the originator for the FP0H(B).
→ Add the FP0H(B) in the scan list and make the connection setting.
• The data stored in the data area (LD30 to 39) of the FP0H(A) is sent to the FP7. The
FP0H(A) is the target for the FP7.
→ Add the tag (Tag_Test1) in the I/O map and register the data area.
• The number of used connections totals two.
3-2
FP7
IP:192.168.1.5
FP0H(A)
IP:192.168.1.6
FP0H(B)
IP:192.168.1.7
Tag_Test1
LD30
LD39
Tag_Test1
LD30
LD39
Tag_Test2
LD40
LD49
Tag_Test2
LD40
LD49
: Sends cyclic data.