The timing that the target sends data is selected from Cyclic or COS (Change of state).
COS is basically a cyclic communication, however, it also performs transmission when
Input Send Trigger
sent data changes.
Some devices do not support COS. The FP0H does not support COS.
Transmission disable time (RPI of input information x 1/4) is displayed when "Input Send
COS Transmission
Trigger" is set to "Change of State (COS)".
Disable Time
Even if the unit detects the change in data, it is not sent within the transmission disable
time.
Parameter setting window appears by pressing the [Parameter Setting] button.
Following screen is example of FP0H.
Parameter setting
Parameters defined in the EDS file can be set.
- The data size of Input Information (T>O) or Output Information (O<T) can be changed.
- The instance ID can be changed (Only for target devices that can be changed).
- Others (Defined in the EDS file)
4.3 Various Setting Screens