7.1 Calculation Method of Load Factor
[Calculation 3] Calculation of unit communication load factor (%)
Calculate it from the number of sent/received packets (pps) and sent/received
data size.
[Example 5] When the number of sent packets is 2000 pps, sent data size is 256
-
bytes,
the number of received packets is 125 pps, and received data size is 86 bytes
Communication load factor (Send) 2000 pps / 5000 pps x 100% = 40%
Communication load factor (Receive) 125 pps / 5000 pps x 100% = 2.5%
The unit communication load factor is (40% + 2.5% = 42.5%).