Connection Using Fp0H As Target - Panasonic AFP0HC32ET User Manual

Ethernet/ip programmable controller
Table of Contents

Advertisement

2.2.2 Connection Using FP0H as Target

Connection 1
Sends data to High-order PLC.
Register the tag/instance information in the "I/O map" of the FP0H.
• The tag/instance information is registered for each originator.
• The high-order PLC (FP7) (originator) makes a connection for the registered tag/instance.
The tag/instance information includes the following information.
• Connected tag/instance
• Data area and size that corresponds to Tag/Instance
When the FP0H is used as target, only the transmission to originator (Input Only) is available.
Once the connection from an originator is established, the FP0H sends data to the originator
from the buffer for the cyclic communication periodically.
KEY POINTS
I/O map is a list for setting the connection information with "Originator".
Use Programming software FPWIN GR7 for the registration.
The EDS file of FP0H can be downloaded from our website.
https://industrial.panasonic.com/ac/e/dl_center/software/
For using the FP0H as a target, the both methods, tag and instance, are
available. However, the selectable instance IDs for the instance method are
100 to 199.
High-order PLC
(FP7)
FP0H
Input Only
2.2 Cyclic Communication of FP0H
Originator
Target
2-7