Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Active Line Modules
5.3 Interface description
NOTICE
Device failure as a result of unshielded or incorrectly routed cables to temperature sensors
Unshielded or incorrectly routed cables to temperature sensors can result in interference
being coupled into the signal processing electronics from the power side. This can result in
significant disturbance of all signals (fault messages) up to failure of individual components
(destruction of the devices).
• Only use shielded cables as temperature sensor cables.
• If temperature sensor cables are routed together with the motor cable, use separately
• Connect the cable shield to ground potential through a large surface area.
• Recommendation: Use suitable Motion Connect cables.
NOTICE
Damage to motor in the event of incorrectly connected KTY temperature sensor
If a KTY temperature sensor is connected with incorrect polarity, it is not possible to detect
when the motor overheats. Overheating can cause damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130, PT1000 or PTC measuring sensor in the stator windings.
Note
Connection to terminal strip -X9
A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and
-X9:7.
116
shielded cables twisted in pairs.
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0