X42 terminal strip

Table 5- 5
Max. connectable cross-section: 2.5 mm
Note
Connection options of terminal strip X42
The terminal strip is not intended to generally provide a 24 V DC supply (for example for
supplying additional components on the plant or system side), as the voltage supply of the
Control Interface Module could also be overloaded and the correct functioning could thus be
compromised.
5.3.7

DRIVE-CLiQ interfaces X400, X401, X402

Table 5- 6
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
Function
1
P24L
2
3
M
4
DRIVE-CLiQ interfaces X400, X401, X402
PIN
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
Technical data
Power supply for Control Unit, Sensor Module
and Terminal Module (18 ... 28.8 V)
maximum load current: 3 A
2
Active Line Modules
5.3 Interface description
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
117