The higher the concentration of heat transfer fluid, the higher the viscosity of the coolant.
This results in a higher pressure loss in the system. See
The nominal current ratings of drive system modules apply to an Antifrogen® L / water
solution of 25/75% (volume). With the Antifrogen® L concentration between 25% and 50%,
the drive output current must be derated by 1/3 percentage point per 1 p.p. increase in
Antifrogen® L concentration. The drawing below shows the derating factor (k) in relation to
Antifrogen® L concentration.
k
1.00
0.95
0.90
25%
30%
35%
Incoming coolant temperature:
0...40 °C (32...104 °F): no drive output current derating required
40...45 °C (104...113 °F): drive output current must be derated by 2 percentage points
per 1 °C (1.8 °F) temperature increase, as shown by curve (a).
45...50 °C (113...122 °F):
If components with a maximum operating temperature of 55 °C (131 °F) are installed
in the same space as the drive modules, drive output current must be derated by
6 percentage points per 1 °C (1.8 °F) temperature increase, as shown by curve (c).
If there are no components with a maximum operating temperature of 55 °C (131 °F)
installed in the same space as the drive modules, drive output current must be
derated by 2 percentage points per 1 °C (1.8 °F) temperature increase, as shown
by curve (b).
The drawing below shows the derating factor (k) in relation to coolant temperature.
The drawing below shows the derating factor (k) in relation to coolant temperature.
k
1.00
0.90
0.80
0.70
0.60
+40 °C
+104 °F
Condensation is not allowed. The minimum coolant temperature to avoid condensation (at
Condensation is not allowed. The minimum coolant temperature to avoid condensation (at
an atmospheric pressure of 1 bar) is shown below as a function of relative humidity (RH)
an atmospheric pressure of 1 bar) is shown below as a function of relative humidity (f) and
and ambient temperature (T
ambient temperature (T
T
air
T
air
(°C)
= 95%
(°C)
5
4.3
10
9.2
5
15
14.2
20
19.2
25
24.1
30
29.1
35
34.1
40%
45%
50% Antifrogen® L concentration
(a)
(b)
(c)
+45 °C
+50 °C
+113 °F
+122 °F
).
).
air
air
= 80%
1.9
RH = 95%
RH = 80%
6.7
4.3
1.9
11.5
16.5
21.4
26.2
31.1
Pressure limits (page
Internal cooling circuit 131
ACS880LC_coolant temp derating curve.pdf
T
Min. T
(°C)
coolant
Min. T
(°C)
coolant
= 65%
= 50%
-0.9
-4.5
RH = 65%
3.7
-0.1
-0.9
8.4
4.6
13.2
9.4
17.9
13.8
22.7
18.4
27.4
23.0
Internal cooling circuit 115
116).
= 40%
-7.4
RH = 50%
RH = 40%
-3.0
-4.5
-7.4
1.5
6.0
10.5
15.0
19.4