Checking The Settings Of The Cooling Fan Transformer; T115 And T125 Tap Settings (690 V Units) - ABB ACS880-207LC Hardware Manual

Igbt supply units
Hide thumbs Also See for ACS880-207LC:
Table of Contents

Advertisement

44 Electrical installation

Checking the settings of the cooling fan transformer

Check the tap settings of all cooling fan transformers. Cooling fan transformers T115 and
T125 are present depending on drive configuration. If the delivery contains an incoming
unit, the cooling fan transformer connections are made at the factory. The connection of
the primary winding of the fan transformer depends on the actual system voltage.
The voltage settings of cooling fan transformers T115 and T125 are made at terminal blocks
T115_X1/X2 and T125_X1/X2 respectively.

T115 and T125 tap settings (690 V units)

T115_X1
T125_X1
690 V
1
660 V
2
600 V
3
575 V
4
540 V
5
525 V
6
7
U1
8
TP1
9
TP2
10
T115_X2
T125_X2
1
230 V
2
3
4
N
5

Advertisement

Table of Contents
loading