Cover the turned shield and the stripped cable with copper foil to keep the shielding
continuous.
A
2
1
5
Note for top entry of cables: When each cable has its own rubber grommet, sufficient IP
and EMC protection can be achieved. However, if very many control cables come to one
cabinet, plan the installation beforehand as follows:
1. Make a list of the cables coming to the cabinet.
2. Sort the cables going to the left into one group and the cables going to the right into
another group to avoid unnecessary crossing of cables inside the cabinet.
3. Sort the cables in each group according to size.
4. Group the cables for each grommet as follows ensuring that each cable has a proper
contact to the cushions on both sides.
Cable diameter in mm
5. Arrange the bunches according to size from thickest to the thinnest between the
5. Arrange the bunches according to size from thickest to the thinnest between the EMI
conductive cushions.
conductive cushions.
6. If more than one cable go through a grommet, seal the grommet by applying Loctite
5221 (catalogue number 25551) inside the grommet.
6. If more than one cable go through a grommet, seal the grommet by applying Loc
5221 (catalogue number 25551) inside the grommet.
Routing the control cables inside the cabinet
Use the existing trunking in the cabinet wherever possible. Use sleeving if cables are
against sharp edges. When running cables to or from the swing-out frame, leave eno
slack at the hinge to allow the frame to open fully.
B
C
A
B
C
2
1
3
2
4
3
4
≤ 13
≤ 17
< 25
≥ 25
Electrical installation 47
Stripped cable
Conductive surface of the shield exposed
Stripped part covered with copper foil
Cable shield
Copper foil
Shielded twisted pair
Grounding wire
Max. number of cables per grommet
4
3
2
1
11
Electrical installatio