8. Attach the conductive sleeves to the cable shields with cable ties. Tie up the unused
conductive sleeves with cable ties.
9. Seal the gap between the cable and mineral wool sheet (if used) with sealing compound
(eg. CSD-F, ABB brand name DXXT-11, code 35080082).
10. Connect the twisted shields of the cables to the PE busbar of the cabinet. Tighten the
screws to the torque given under
11. Connect the phase conductors of the input cable to the L1, L2 and L3 terminals. Tighten
the screws to the torque given under
12. Reinstall the shrouding removed earlier.
13. Close the cubicle door.
Tightening torques (page
Tightening torques (page
Electrical installation 41
101).
101).