Planning
4

Site survey

4.2 Site survey

4.3 Calculating the details of the pipe system

32 | 56
Building Technologies
Fire Safety
6. Check that the requirements have been met.
The necessary sensitivity for the aspirating smoke system has been achieved.
The planning limits have been observed.
The environmental requirements at the installation location have been taken
into account.
The customer requirements have been met.
Carry out a site survey to gather essential information for planning the pipe system.
This information involves much more than simply measuring the physical size of
the fire zone.
Gather information about the following:
Properties (material and surface) of:
Walls
Floors
Ceilings
Furniture
Decoration
Types of room within the fire compartment
Type of heating
Floor heating
Overhead heating
Radiant heaters
Air conditioning unit
Cavities
False floor
False ceiling
Channels
Ducts
Room geometry in the fire zone
Boundaries of the fire zone
Availability of current building plans
Dust load in the environment to be monitored
The final stage of the planning process is to calculate the proposed design using
the 'FXS2056 ASD Asyst Tool V2' software.
Use the data obtained on site as the basis for your calculation. A calculation must
be performed with the 'FXS2056 ASD Asyst Tool V2' software prior to each
installation.