Siemens FDA241 Planning, Mounting page 38

Asd pipe system
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Planning
4
Pipe system
FDA221
38 | 56
Building Technologies
Fire Safety
Topology and length of pipe branches
Short pipe branches result in a quick response time.
Preferably, you should select short pipe branches. You can achieve this by
using a U-topology or double U-topology.
Remember to adhere to the maximum permissible number of pipe branches
and the total length for the pipe system.
You will find more information in chapter 'Limits to planning [
max. 30 m
max. 25 m
max. 25 m
Figure 11: Permissible topologies and pipe lengths
FDA241
40]'.
max. 60 m
max. 60 m
max. 60 m
max. ... m
max. ... m
max. ... m
max. 30 m
max. 30 m
max. 30 m
max. 30 m
A6V10334435_g_en_--