Branches And Bends; End Caps; Label For Aspirating Holes - Siemens FDA241 Planning, Mounting

Asd pipe system
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

System description
3
Components of the pipe system

3.7.2 Branches and bends

3.7.3 End caps

3.7.4 Label for aspirating holes

28 | 56
Building Technologies
Fire Safety
90° bend
T-piece
An end cap must be glued to every open end in the pipe system.
End cap
Label
For changes of direction in the pipe system
90° bend angle
Flange for holding the pipe at both ends
The pipes are glued to the bend
Recommendation: Use a bend with the largest
possible radius, e.g., 70 mm
Material: Typically PVC or ABS depending on
the ambient conditions
For branches in the pipe system
Flange for holding the pipe at all three ends
The pipes are glued to the T-piece
Material: Typically PVC or ABS depending on
the ambient conditions
For fitting on a free pipe end
The end cap is glued to the pipe
Material: Typically PVC or ABS depending on
the ambient conditions
For identifying aspirating holes on pipes
Self-adhesive
Dimensions: 95 x 24 mm, hole diameter 9 mm
A6V10334435_g_en_--
2017-09-12