4.7 Network for monitored area
Building Technologies
Fire Safety
Create a network of aspirating holes that covers the area to be monitored.
Figure 8: Determining the position of the aspirating holes
1 Aspirating hole
Determine the position and topology of the pipes.
2.5 m
5 m
5 m
Figure 9: Determining the position of the pipes and the aspirating smoke detector
1 Aspirating smoke detector
2
Pipe
Network for monitored area
2
Mains
5 m
5 m
2.5 m
3
Network with a mesh size of 5 m
4
Aspirating hole
Planning
4
1
2
2.5 m
1
5 m
2
5 m
3
5 m
4
2.5 m
35 | 56
A6V10334435_g_en_--
2017-09-12