Beko BX 109 C Installation Manual page 13

Mobile room air conditioner
Hide thumbs Also See for BX 109 C:
Table of Contents

Advertisement

Available languages

Available languages

1
Safety precautions
is necessary to continue operation, an adequate temporary
solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
• T hat capacitors are discharged: this shall be done in a safe manner
to avoid possibility of sparking.
• T hat no live electrical components and wiring are exposed while
charging, recovering or purging the system.
• K eep continuity of earthing.
Inspection of cable
Check the cable for wear, corrosion, overvoltage, vibration and
check if there are sharp edges and other adverse effects in the
surrounding environment. During the inspection, the impact of
aging or the continuous vibration of the compressor and the fan on
it should be taken into consideration.
Leakage check of R290 refrigeral
Note: Check the leakage of the refrigerant in an
C
environment where there is no potential ignition source.
No halogen probe (or any other detector that uses an
open flame) should be used.
Leak detection method:
For systems with refrigerant R290, electronic leak detection
instrument is available to detect and leak detection should not be
conducted in environment with refrigerant. Make sure the leak
Mobile room air conditioner / Installation Manual
13 / 88 EN