Total Current Feedback Unhealthy; Internal Reference Current Unhealthy; Individual Current Too High Relative To Total Current - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

46-47
Description Output [ ] total current feedback unhealthy
Possible Cause
Commanded output is beyond the range of the output.
Field wiring problem
Field device problem
Open loop or too much resistance in the loop.
Solution
Verify that the commanded output is within the range of the output.
Confirm the correct I/O pack 28 V input power.
Check the field wiring and the component.
Replace the I/O pack.
48-49
Description Output [ ] Internal reference current unhealthy
Possible Cause I/O pack failure
Solution
Confirm the correct I/O pack 28 V input power.
Replace the I/O pack.
66-67
Description Output [ ] Individual current too high relative to total current
Possible Cause In a TMR setup, the individual current feedback is greater than ½ the total current feedback + TMR_
SuicLimit.
The TMR_SuicLimit is set too low.
Hardware failure causing one I/O pack to drive too much output current
Solution
Verify that the value of TMR_SuicLimit is set correctly.
Replace the I/O pack.
102
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information