Firmware Error - Internal Process Failed; Unexpected Reboot Occurred - Hardware Fault - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

284
Description

Firmware error - Internal process failed

Possible Cause
Runtime or hardware malfunction (runtime process failed)
Solution
Reload the firmware and application, and restart the controller and/or I/O module.
Re-download the baseload and the firmware.
If this does not work, replace the I/O module or controller.
285
Description

Unexpected reboot occurred - hardware fault

Possible Cause
Runtime or hardware malfunction
Runtime process stalled
Note This diagnostic alarm is detected on a processor startup after the processor or hardware has malfunctioned and caused
a processor to reboot. Therefore, the diagnostic alarm timestamp may be delayed from when the actual fault occurred.
Solution
Reload firmware and application and restart.
If the problem persists, replace the processor module.
292
Description Application Error - application overrunning the frame
Possible Cause Application cannot start within frame.
Solution Check application loading and reduce the amount of application code or frequency of execution. Build
application and download to all controllers.