Ionet-Egd - Received Redundant Exchange From Unknown Address; Ionet-Egd - Out Of Order Exchange; Ionet-Egd - Unhealthy - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

274
Note This alarm is obsolete.
Description IONET-EGD - Received Redundant Exchange from unknown address
Possible Cause Controller received EGD message from unknown address
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
275
Note This alarm is obsolete.
Description IONET-EGD - Out of order Exchange [ ] from Producer [ ], Rcvd [ ], Last [ ]
Possible Cause Message sequence number was out of order, less than required
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
276
Note This alarm is obsolete.
Description IONET-EGD - UNHEALTHY (Bad Configuration Time) Producer [ ], Exchange [ ]
Possible Cause Message version mismatch
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
458
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II