STAI
STAI
Channel
Screw
Name
40
Ret
10
41
PCOM
42
PCOM
43
PCOM
44
PCOM
45
OP1
11
46
OR1
11
47
OP2
12
48
OR2
12

7.3.3.3 Wiring and Configuration for STAO Retrofits

The following table provides a field wiring and channel comparison for retrofitting an existing STAO with a SUAA terminal
board to provide current outputs.
YUAA Universal I/O Modules
SUAA
SUAA
screw
Name
30
IO-
49
COM
50
COM
51
COM
52
COM
33
IO+
35
IO-
34
IO+
36
IO-
STAO
STAO
Channel
Screw
Name
1
AO
1
2
Ret
1
3
AO
2
4
Ret
2
5
AO
3
6
Ret
3
7
AO
4
8
Ret
4
9
AO
5
10
Ret
5
11
AO
6
12
Ret
6
13
AO
7
14
Ret
7
15
AO
8
16
Ret
8
17
Chassis Ground
18
Chassis Ground
19-36
No connects
Public Information
Use
Same as SUAA screw 5
Ground for special-use 4-wire internally powered devices
Ground for special-use 4-wire internally powered devices
Ground for special-use 4-wire internally powered devices
Ground for special-use 4-wire internally powered devices
current output 1
return for current output 1
current output 2
return for current output 2
SUAA
SUAA
Screw
Name
3
IO+
5
IO-
4
IO+
6
IO-
9
IO+
11
IO-
10
IO+
12
IO-
15
IO+
17
IO-
16
IO+
18
IO-
21
IO+
23
IO-
22
IO+
24
IO-
Chassis
Chassis
n/c
Use
AO Signal
Return
AO Signal
Return
AO Signal
Return
AO Signal
Return
AO Signal
Return
AO Signal
Return
AO Signal
Return
AO Signal
Return
GEH-6855_Vol_II System Guide 181