7.5 Analog Inputs (Voltage or mA Current)

There are three connections per analog channel providing local power output with current limiting (PWR_RTN), IO+ signal,
and IO- signal/return as needed for each functional mode (4–20 mA, ± 5 V dc, or ± 10 V dc). The following figures provide
typical wiring options.
Note HART is optional for all internally powered mA input modes. HART is not supported for externally powered devices.
Caution
188
GEH-6855_Vol_II

Analog Inputs Wiring Options

Internally powered 2 or 3 wire devices use the analog output DAC set at 24 mA. While
there is no thermal derating for number of active analog outputs at ambients up to 70° °
C (158 ° ° F), it is possible for a fault condition with shorted leads to cause all power
dissipation to be within the YUAA package. In this situation, there may be thermal
alarms annunciated for the processor board.

GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II

Public Information