Communication Lost From S Processor; Communication Lost From T Processor - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

327
Description Communication lost from S processor
Possible Cause
IONet or hardware malfunction
R or T processor in redundant system lost communication with S processor
Missing cable from the controller to the Unit Data Highway (UDH) network switch
Solution
Go online with the S processor. Verify that the processor is in the Controlling state. If not communicating or in
Controlling state, restart the processor.
Check for disconnected IONet cables or malfunctioning switches.
Rebuild and download the application.
Check for a defective Ethernet cable to network switch.
Check for a defective network switch:
Place the Ethernet cable into empty port.
If the problem persists, replace the network switch.
328
Description Communication lost from T processor
Possible Cause
IONet or hardware malfunction
R or S processor in redundant system lost communication with T processor
Missing cable from the controller to the Unit Data Highway (UDH) network switch
Solution
Go online with the T processor. Verify that the processor is in the Controlling state. If not communicating or in
Controlling state, restart the processor.
Check for disconnected IONet cables or malfunctioning switches.
Rebuild and download the application.
Check for a bad Ethernet cable to network switch.
Check for a bad network switch:
Place the Ethernet cable into empty port.
If the problem persists, replace the network switch.
50
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents