ABB Relion 670 Series Product Manual page 37

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Bay control REC670
Version 2.2
Rate-of-change of frequency protection SAPFRC
The rate-of-change of frequency protection function
(SAPFRC) gives an early indication of a main disturbance
in the system. SAPFRC measures frequency with high
accuracy, and can be used for generation shedding, load
shedding and remedial action schemes. SAPFRC can
discriminate between a positive or negative change of
frequency. A definite time delay is provided for operate.
SAPFRC is provided with an undervoltage blocking. The
operation is based on positive sequence voltage
measurement and requires two phase-phase or three
phase-neutral voltages to be connected.
Frequency time accumulation protection FTAQFVR
Frequency time accumulation protection (FTAQFVR) is
based on measured system frequency and time
counters. FTAQFVR for generator protection provides
the START output for a particular settable frequency
limit, when the system frequency falls in that settable
frequency band limit and positive sequence voltage
within settable voltage band limit. The START signal
triggers the individual event timer, which is the
continuous time spent within the given frequency band,
and the accumulation timer, which is the cumulative
time spent within the given frequency band. Once the
timers reach their limit, an alarm or trip signal is
activated to protect the turbine against the abnormal
frequency operation. This function is blocked during
generator start-up or shut down conditions by
monitoring the circuit breaker position and current
threshold value. The function is also blocked when the
system positive sequence voltage magnitude deviates
from the given voltage band limit which can be enabled
EnaVoltCheck setting.
by
It is possible to create functionality with more than one
frequency band limit by using multiple instances of the
function. This can be achieved by a proper configuration
based on the turbine manufacturer specification.
12. Multipurpose protection
General current and voltage protection CVGAPC
The General current and voltage protection (CVGAPC)
can be utilized as a negative sequence current
protection detecting unsymmetrical conditions such as
open phase or unsymmetrical faults.
CVGAPC can also be used to improve phase selection for
high resistive earth faults, outside the distance
protection reach, for the transmission line. Three
functions are used, which measures the neutral current
and each of the three phase voltages. This will give an
independence from load currents and this phase
selection will be used in conjunction with the detection
Hitachi Power Grids
M14965-3 v14
GUID-020CE8CF-9BEA-455D-ACBD-13023B93B4D1 v5
M13083-11 v9
© Copyright 2017 Hitachi Power Grids. All rights reserved
of the earth fault from the directional earth fault
protection function.
13. General calculation
Multipurpose filter SMAIHPAC
The multi-purpose filter function block (SMAIHPAC) is
arranged as a three-phase filter. It has very much the
same user interface (e.g. inputs and outputs) as the
standard pre-processing function block SMAI. However
the main difference is that it can be used to extract any
frequency component from the input signal. Thus it can,
for example, be used to build sub-synchronous
resonance protection for synchronous generator.
14. Secondary system supervision
Current circuit supervision CCSSPVC
Open or short circuited current transformer cores can
cause unwanted operation of many protection functions
such as differential, earth-fault current and negative-
sequence current functions.
Current circuit supervision (CCSSPVC) compares the
residual current from a three phase set of current
transformer cores with the neutral point current on a
separate input taken from another set of cores on the
current transformer.
A detection of a difference indicates a fault in the circuit
and is used as alarm or to block protection functions
expected to give inadvertent tripping.
Fuse failure supervision FUFSPVC
The aim of the fuse failure supervision function
(FUFSPVC) is to block voltage measuring functions at
failures in the secondary circuits between the voltage
transformer and the IED in order to avoid inadvertent
operations that otherwise might occur.
The fuse failure supervision function basically has three
different detection methods, negative sequence and
zero sequence based detection and an additional delta
voltage and delta current detection.
The negative sequence detection algorithm is
recommended for IEDs used in isolated or high-
impedance earthed networks. It is based on the
negative-sequence quantities.
The zero sequence detection is recommended for IEDs
used in directly or low impedance earthed networks. It is
based on the zero sequence measuring quantities.
The selection of different operation modes is possible
by a setting parameter in order to take into account the
particular earthing of the network.
1MRK 511 404-BEN N
GUID-EB0B11C3-FF79-4B8D-A335-649623E832F9 v3
M12444-3 v10
SEMOD113820-4 v13
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents