ABB Relion 670 Series Product Manual page 64

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Bay control REC670
Version 2.2
Table 26. Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence,
operate value
Interrupted auxiliary DC voltage
Interruption
interval
0–50 ms
0–∞ s
Restart time
Table 27. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Harmonic frequency dependence (20% content)
Harmonic frequency dependence for high impedance differential
protection (10% content)
Harmonic frequency dependence for overcurrent protection
64
Reference value
Within nominal
range
max. 2%
15% of EL
Full wave
rectified
±20% of EL
24-60 V DC ± 20%
90-250 V DC ± 20%
Within nominal range
f
r
f
r
2
2
2
© Copyright 2017 Hitachi Power Grids. All rights reserved
Influence
0.01%/%
0.01%/%
No restart
Correct behaviour at power down
< 300 s
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
nd
rd
th
, 3
and 5
harmonic of f
r
nd
th
, 3rd and 5
harmonic of f
r
nd
rd
th
, 3
and 5
harmonic of f
r
1MRK 511 404-BEN N
Influence
±1.0%/Hz
±2.0%
±10.0%
±3.0%
Hitachi Power Grids

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents