ABB Relion 670 Series Product Manual page 80

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Bay control REC670
Version 2.2
Table 52. Voltage-restrained time overcurrent protection VRPVOC
Function
Start overcurrent
Reset ratio, overcurrent
Operate time, start overcurrent at 0 to 2 x
I
set
Reset time, start overcurrent at 2 x I
Operate time, start overcurrent at 0 to 10
x I
set
Reset time, start overcurrent at 10 x I
0
Independent time delay to operate at 0 to
2 x I
set
Inverse time characteristics,
see tables
170
and
171
Minimum operate time for inverse time
characteristics
High voltage limit, voltage dependent
operation
Start undervoltage
Reset ratio, undervoltage
Operate time start undervoltage at 2 x U
to 0
Reset time start undervoltage at 0 to 2 x
U
set
Independent time delay to operate,
undervoltage at 2 x U
to 0
set
Internal low voltage blocking
Overcurrent:
Critical impulse time
Impulse margin time
Undervoltage:
Critical impulse time
Impulse margin time
80
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8
Range or value
(2.0 - 5000.0)% of IBase
> 95%
Min. = 15 ms
Max. = 30 ms
to 0
Min. = 15 ms
set
Max. = 30 ms
Min. = 5 ms
Max. = 20 ms
to
Min. = 20 ms
set
Max. = 35 ms
(0.00 - 6000.00) s
13 curve types
(0.00 - 60.00) s
(30.0 - 100.0)% of UBase
(2.0 - 100.0)% of UBase
< 105%
Min. = 15 ms
set
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
(0.00 - 6000.00) s
(0.0 - 5.0)% of UBase
10 ms typically at 0 to 2 x I
15 ms typically
10ms typically at 2 x U
15 ms typically
© Copyright 2017 Hitachi Power Grids. All rights reserved
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
-
±0.2% or ±35 ms whichever is greater
See tables
170
and
±0.2% or ±35 ms whichever is greater
±1.0% of U
r
±0.5% of U
r
-
-
-
±0.2% or ±35 ms whichever is greater
±0.25% of U
r
-
set
-
to 0
set
1MRK 511 404-BEN N
171
Hitachi Power Grids