ABB Relion 670 Series Product Manual page 97

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Bay control REC670
Version 2.2
Table 74. Autorecloser SMBRREC
Function
Dead time:
shot 1 "t1 1Ph"
shot 1 "t1 2Ph"
shot 1 "t1 3Ph "
shot 1 "t1 3PhHS"
Dead time:
shot 2 "t2 3Ph"
shot 3 "t3 3Ph"
shot 4 "t4 3Ph"
shot 5 "t5 3Ph"
Extend three-phase dead time duration "tExtended t1"
Minimum time that circuit breaker must be closed before new sequence is allowed
"tCBClosedMin"
Wait time for the slave to close when WAIT input has reset "tSlaveDeadTime"
Maximum allowed start pulse duration "tLongStartInh"
Circuit breaker closing pulse duration "tPulse"
Reclaim time "tReclaim"
Maximum wait time for release from master "tWaitForMaster"
Reset time for reclosing inhibit "tInhibit"
Wait time after close command before proceeding to next shot "tAutoContWait"
Maximum wait time for fulfilled synchrocheck conditions "tSync"
Delay time before indicating successful reclosing "tSuccessful"
Maximum wait time for circuit breaker closing before indicating unsuccessful
"tUnsucCl"
Hitachi Power Grids
M12379-1 v13
© Copyright 2017 Hitachi Power Grids. All rights reserved
1MRK 511 404-BEN N
Range or value
Accuracy
(0.000-120.000) s
±0.2% or ±35 ms
whichever is greater
(0.00-6000.00) s
±0.2% or ±35 ms
whichever is greater
(0.000-60.000) s
±0.2% or ±35 ms
whichever is greater
(0.00-6000.00) s
±0.2% or ±35 ms
whichever is greater
(0.100-60.000) s
±0.2% or ±35 ms
whichever is greater
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
(0.00-6000.00) s
±0.2% or ±15 ms
whichever is greater
(0.00-6000.00) s
±0.2% or ±15 ms
whichever is greater
(0.000-60.000) s
±0.2% or ±45 ms
whichever is greater
(0.000-60.000) s
±0.2% or ±45 ms
whichever is greater
(0.00-6000.00) s
±0.2% or ±45 ms
whichever is greater
(0.000-60.000) s
±0.2% or ±50 ms
whichever is greater
(0.00-6000.00) s
±0.2% or ±45 ms
whichever is greater
97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents