Mitsubishi Electric MELSEC iQ-R Series Migration Manual page 42

Servo system controller motion controller
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2. DETAILS OF MIGRATION FROM Q17nCPUN(-T) TO RnMTCPU
(4) Items that need a review or a change following the servo system network change
Items
System setting/
SSCNET configuration
Electronic gear
Powering OFF a servo
If a servo amplifier is turned OFF,
amplifier in the same
there is no influence on the other
network line
servo amplifiers in the same
network line.
Connect/disconnect of
No special operation is required to
SSCNET communication
turn OFF/ON a servo amplifier in
the SSCNET network line.
Battery disconnection
Servo error code
warning,
2102(9F): Battery warning
Battery warning
2103(92): Battery disconnection
Main circuit OFF
If the main circuit is turned OFF
warning
while the servo OFF command
(M3215+20n) is ON, the main
circuit OFF warning 2149(E9) will
not occur.
Differences
Q17nCPUN(-T)
Q173CPUN(-T): 4 lines
(Up to 8 axes/line)
Q172CPUN(-T): 1 line
(Up to 8 axes/line)
warning
RnMTCPU
R32MTCPU: 2 lines
(Up to 16 axes/line)
R16MTCPU: 1 line
(Up to 16 axes/line)
If a servo amplifier is turned OFF
in the same network, the servo
amplifiers connected after that one
cannot be used.
Use the connect/disconnect
function of SSCNET to turn
OFF/ON a servo amplifier in the
SSCNET network line.
Warnings
0C80(9F.1): Low battery
0C80(92.1): Encoder battery cable
disconnection
warning
If the main circuit is turned OFF
while the servo OFF command
(M3215+20n) is ON, the [OC80
(E9.3): Ready-on signal on during
main circuit off] will be turned ON.
2 - 10
Changes/revisions
Set the servo amplifier's rotary switch
and connection according to the
SSCNET configuration.
Change "Number of pulses per
revolution" and "Movement amount per
revolution" of the fixed parameters
according to the resolution per the
connected servo motor revolution.
Use MR-MV200 SSCNETIII/H
compatible optical hub unit.
This function disconnects the network
connection of the servo amplifiers after
the disconnected one.
In order to turn off only a specific servo
amplifier, use MR-MV200 SSCNETIII/H
compatible optical hub unit.
Revise the program if it uses the servo
error code on the left.
The warning occurs when the main
circuit is turned OFF while the servo
OFF command (M3215+20n) is ON.
In order not to let the [OC80 (E9.3):
Ready-on signal on during main circuit
off] turn ON, change the PC18 servo
parameter from "0000(H)" to
"1000(H)".