Operation Of The Line Connection Components Via An Autotransformer - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line connection
4.13 Line connection variants
4.13.3

Operation of the line connection components via an autotransformer

An autotransformer can be used to adapt the voltage in the range up to 3-ph. 480 V AC
+10 %.
To ensure protective separation an isolating transformer must be used for voltages greater
than 3-ph. AC 480 V AC +10 %.
Applications:
● The motor insulation must be protected from excessive voltages.
● The active line module must provide a stabilized DC link voltage. This is possible with a
102
DANGER
rated voltage of 380 V to 415 V.
A combination with motors that may be operated with a DC link voltage of up to 660 V,
and a line voltage > 415 V requires a controlled DC link voltage.
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4