Removing The Dc Link Busbars; Mounting The Reinforced Dc Link Busbars - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

13.4.3

Removing the DC link busbars

Unscrew the screws for the DC link busbar
Remove the DC link busbars on the adjacent components
too.
13.4.4

Mounting the reinforced DC link busbars

Secure the reinforced DC link busbars Do not secure M4
screws tightly yet.
Tightly secure all the M4 screws,
1.8 Nm +30 %
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
Remove the DC link busbars
View once the DC link busbars have been removed
Secure the reinforced DC link busbars on the adjacent
components too.
With installed reinforced DC link busbars
Accessories
13.4 Reinforced DC-link busbars
291