X21/X22 Ep Terminals / Temperature Sensor Connection For Motor Module With Cold Plate; X200-X203 Drive-Cliq Interface - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules with Cold Plate
8.3 Interface description
8.3.4
X21/X22 EP terminals / temperature sensor connection for motor module with cold
plate
Table 8-3
Terminal block X21/X22
Terminal
1
2
3
4
Max. connectable cross-section 1.5 mm
Type: Screw terminal 1 (see Appendix A)
NOTICE
The KTY temperature sensor must be connected with the correct polarity.
Note
The temperature sensor connection is required for motors where the temperature value is
not transmitted via DRIVE-CLiQ.
If the Safety function is active, 24 V DC must be connected to terminal 3 and ground to
terminal 4. When removed, pulse inhibit is activated (if this has been parameterized).
8.3.5

X200-X203 DRIVE-CLiQ interface

Table 8-4
DRIVE-CLiQ interface X200-X202: single motor module
DRIVE-CLiQ interface X200-X203: double motor module
Pin
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Yamaichi, order no.: Y-ConAS-13
186
Function
+Temp
-Temp
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
2
Name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical specifications
Temperature sensor connection KTY84–1C130
Supply voltage: 24 V DC (20.4 V - 28.8 V)
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
H → L: 1000 μs
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4