X200-X202 Drive-Cliq Interfaces; X2 Braking Resistor Connection - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.3.5

X200-X202 DRIVE-CLiQ interfaces

Table 6-5
DRIVE-CLiQ interface X200-X202
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Fa. Yamaichi, Bestellnummer: Y-ConAS-13
6.3.6

X2 braking resistor connection

Table 6-6
Terminal block X2 on Basic Line Module (20 kW)
Terminal
1
2
Table 6-7
Terminal block X2 on Basic Line Module (40 kW)
Terminal
1
2
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Designation
Braking resistor connection R
Designation
Braking resistor connection R
Basic Line Modules with cold plate
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Technical specifications
Max. connection voltage:
480 V 3 AC +10 % at 47 Hz to 63 Hz
Max. connectable cross-section: 4 mm
Type: Screw terminal 5 (see Connection Methods)
Tightening torque: 0.5 - 0.6 Nm
Technical specifications
Max. connection voltage:
480 V 3 AC +10 % at 47 Hz to 63 Hz
Max. connectable cross-section: 10 mm
Type: Screw terminal 6 (see Connection Methods)
Tightening torque: min 1.5 - 1.8 Nm