X41 Ep Terminals; X42 Terminal Strip; Drive-Cliq Interfaces X400, X401, X402 - Siemens SINAMICS S120 Equipment Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
3.2 Basic Line Modules
3.2.3.5

X41 EP terminals

Table 3- 4
X41 terminal strip
Terminal
4
3
2
1
Max. connectable cross-section 1.5mm
Note
For operation, 24 V DC must be connected to terminal 2 and ground to terminal 1. Pulse
suppression is activated when terminals are disconnected.
3.2.3.6

X42 terminal strip

Reserved, do not use!
3.2.3.7

DRIVE-CLiQ interfaces X400, X401, X402

Table 3- 5
DRIVE-CLiQ interfaces X400, X401, X402
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Yamaichi, order no.: Y-ConAS-13
78
Function
Not assigned
Not assigned
EP +24 V (enable pulses)
EP M1 (enable pulses)
2
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical specifications
Supply voltage: 24 V DC (20.4 V – 28.8 V)
Power consumption: 10 mA
Signal propagation times:
L → H 100 μs
H → L: 1000 μs
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3