Cabinet design and EMC
7.3 Cabinet air conditioning
With degrees of protection higher than IP20 and if a hood is used, it may be necessary to
use an "active" hood. An "active" hood contains fans that blow the air current forwards. The
hood is closed, with the exception of the air outlet point.
If you choose an "active" hood, you must ensure that the fans are sufficiently powerful to
prevent air from accumulating in the cabinet. If air accumulates, the cooling capacity is
reduced. This can overheat and destroy the devices. The air capacity of the fans should at
least be equivalent to the device fan data.
Table 7- 6
Volume flow rate, opening cross-sections
Order number
6SL3300
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet
inlet
[m²]
outlet
[m²]
Order number
6SL3330
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet
inlet
[m²]
outlet
[m²]
Order number
6SL3330
Cooling air
[m³/s]
requirement
Min. opening
cross-section in
cabinet
inlet
[m²]
outlet
[m²]
258
7TE32-6AA0
7TE33-8AA0
7TE35-0AA0
0.24
0.1
0.1
1TE34-2AA0
1TE41-2AA0
-
1TE35-3AA0
1TE41-5AA0
1TE38-2AA0
1TH41-1AA0
1TH33-0AA0
1TH41-4AA0
1TH34-3AA0
1TH36-8AA0
0.17
0.1
0.1
6TE35-5AA0
6TE41-1AA0
-
6TE37-3AA0
6TG38-8AA0
6TG35-5AA0
0.36
0.16
0.16
Active Interface Module
7TE38-4AA0
7TE41-4AA0
7TG35-8AA0
7TG37-4AA0
7TG41-3AA0
0.47
0.4
0.20
0.16
0.20
0.16
Basic Line Module
0.36
0.16
0.16
Smart Line Module
6TE41-3AA0
6TE41-7AA0
6TG41-2AA0
6TG41-7AA0
0.78
1.08
0.28
0.4
0.28
0.4
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3