Line Modules
3.3 Smart Line Modules
3.3.3.3

Line/load connection

Table 3- 14
Line/load connection of the Smart Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
PE1, PE2
100
Technical specifications
Voltage:
3-ph. 380 V AC -10 % (-15 % < 1 min) to 3-ph. 480 V AC +10 %
3-ph. 500 V AC -10 % (-15 % < 1 min) to 3-ph. 690 V AC +10 %
Frequency: 47 Hz to 63 Hz
Connecting thread:
Frame size GX: M10 / 25 Nm for ring cable lugs to DIN 46234
Frame sizes HX / JX: M12 / 50 Nm for ring cable lugs to DIN 46234
Voltage:
500 V to 630 V DC
650 V to 900 V DC
Connections:
Frame size GX: Threaded bolt M6 / 6 Nm for ring cable lugs to DIN 46234
Frame sizes HX / JX: d = 13 mm (M12/50 Nm) flat connector for busbar
Voltage:
500 V to 630 V DC
650 V to 900 V DC
Connections:
Frame size GX: Thread M10 / 25 Nm for ring cable lugs to DIN 46234
Frame sizes HX / JX: d = 13 mm (M12/50 Nm) flat connector for busbar
Connecting thread:
Frame size GX: M10 / 25 Nm for ring cable lugs to DIN 46234
Frame sizes HX / JX: M12 / 50 Nm for ring cable lugs to DIN 46234
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3