Electrical Connection - Siemens SINAMICS S120 Equipment Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
3.2 Basic Line Modules
3.2.5

Electrical connection

Operating a Basic Line Module from an insulated network (IT system)
When the device is operated on an isolated-neutral network (IT system), the connection
bracket to the noise suppression capacitor must be removed (e.g.: see "1" in figure below).
The interface overview in the section "Interface description" shows the position of the
connection bracket on the different frame sizes.
Figure 3-6
Failing to remove the connection bracket for the noise suppression capacitor on a non-
grounded system/IT system can cause significant damage to the unit.
82
Removing the connection bracket to the noise suppression capacitor (example: frame
size FB)
WARNING
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3