Home Settings Sensor settings A1 right arrow (2. page) Gas constant
The remaining text fields can be labelled and configured in the same manner. For details, see chapter 11.2.2.7 Labelling and
configuring text fields!
Home Settings Sensor settings A1 right arrow (2. page)
Note:
After confirming with OK, the field labels change back to black and the settings are applied.
Caution:
Reference temperature and reference pressure (factory settings 20°C, 1000 hPa): All volume flow (m³/h) and
consumption (m³) values shown on the display refer to 20°C and 1000 hPa (according to ISO 1217). Alternatively, enter
0°C and 1013 hPa (=standard cubic metre according to DIN 1343) as the reference values. Do not enter the operating
pressure or the operating temperature as the reference values!
METPOINT
BDL compact
®
Installation and operating manual
Preselection of matching Units.
If a text field is displayed with red text, the
respective values (e.g. Diameter or Name) have been
changed.