Removal Of The Automatic Louver Motor - Hitachi RCI Service Manual

Indoor units system free series & complementary systems
Table of Contents

Advertisement

10 Servicing

10.2.13 Removal of the automatic louver motor

Remove the optional air panel in line with the instructions given in
chapter
Removal of the optional air
panel, see on page 278.
Separate the connector from the AS motor.
Remove the screw securing the louver and one set screw on the
AS motor.
Remove the AS motor, pulling carefully with the louver and then
sliding it out.
After removing the AS motor, refit the louver adjusting the stop
position as indicated in the figure: cut D on the shaft of the AS motor
must coincide with cut D on the louver.
286
SMGB0063 rev. 1 - 10/2010