Step 3 Pull the water pan cover outward.
Figure 4-32 Pulling the water pan cover outward
Step 4 Remove the two screws that secure the sheet metal fastener of the liquid level
detector, disconnect the interconnection terminal of the liquid level detector, and
then remove the sheet metal fastener of the liquid level detector.
Figure 4-33 Removing screws from the sheet metal fastener of a liquid level
detector
Step 5 Use a Phillips screwdriver to remove the screws that secure the high liquid level
detector, and remove the high liquid level detector (the low liquid level detector
can be taken out by rotating it).