FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Store the removed screws and fasteners. Reinstall them after maintenance.
Step 2 Remove the sliding base fasteners for other cabinets inside the pre-fab. module in
the same way.
Figure 3-8 Removing the cabinet sliding base fasteners
----End

3.3 Daily Maintenance

Table 3-2 Daily maintenance checklist
Categor
Maintenan
y
ce Item
Power
Integrated
supply
UPS
and
distribut
ion
system
ECC800-
FusionDC1
Pro
000 alarms
WebUI
Issue 01 (2021-04-20)
CA UTION
Method
Observe the power
input status
indicator.
On the ECC800-Pro
WebUI, choose
Home > Active
Alarms or Query >
Historical Alarms.
Copyright © Huawei Technologies Co., Ltd.
Check Standard
Troubleshooting
Observe the
If the input voltage is
indicator
abnormal, check the power
luminance, the
grid status and input cable
indicators are on.
connection.
If the power supply is normal
but an indicator is off or
generates dim light, replace
the indicator.
No alarm is
Clear alarms by referring to
displayed in the
the ECC800-Pro documents.
alarm information
area.
3 Routine Maintenance
25