3.6.5 Fire Extinguishing System (CE)

● Semi-annual maintenance of the fire extinguishing system involves system
commissioning. Before the maintenance, inform the related administrative
departments that the fire extinguishing system will be maintained and stop
working.
● Before maintaining the fire extinguishing system, remove the electrical actuator
from the container valve of the fire cylinder. This prevents the extinguishant
release due to misoperations, and prevents accidental damage.
● After the maintenance, reconnect the electrical actuator, and inform the
administrative departments that the fire extinguishing system has become
operational.
Table 3-18 Semi-annual maintenance checklist for the fire extinguishing system
Device
Method
Fire
Commission the fire
extinguishing
extinguishing system
system
by following the
commissioni
instructions in the
ng
Fire Extinguishing
System
Commissioning (CE)
section in the
commissioning guide
for the solution in
use.
Fire alarm
Flip the key to
bell
Enable Control on
the extinguishant
control panel
rightward. Press
Silence/Sound
Alarm to start or
abort the fire alarm
bell. Reset the key to
Enable Control by
flipping it leftward.
Issue 01 (2021-04-20)
NO TICE
Check Standard
Devices work properly, and the
management system displays
related alarms.
The alarm bell rings normally.
The alarm bell rings loud and
clear when it is started.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Maintenance Guide
Replace the
corresponding
component.
1. Check and reconnect
cables to the fire
alarm bell.
2. If the fault persists,
replace the fire alarm
bell.