Download Print this page

Mitsubishi Electric Y Series Manual page 134

Hide thumbs Also See for Y Series:

Advertisement

Ceiling concealed type
134
Low static pressure type
PEFY-P VMS1(L)-E
• Technologies and functions
A thin body 200 mm in height and a maximum external static
pressure rating of 50 Pa provides significant flexibility of design
and allows installation in narrow ceiling spaces.
The lineup consists of models up to P63 with the same height.
Compact design with a height of no
more than 200 mm
of 790 mm
(P15-P32)
The thin body with a height of no more than 200 mm (all models)
allows installation in a ceiling with small cavity space.
PEFY-P VMS1(L)-E
Height
Height
mm
mm
Width
mm
Optional drain pump
For PEFY-P VMS1, the drain pump is equipped as a standard
feature and eliminates the need for a drain trap. It has a
maximum lifting height of 550 mm.
For PEFY-P VMS1L-E, the drain pump is sold separately.
*For places where low noise operation is especially required (i.e., hotels), VMS1L
(without drain pump) is recommended.
∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙ P.167
and widths
(all models)
.
Height
200 mm
(all models)
P15
P20
P25
P32
P40
P50
200
790
990
VMS1
VMS1L
Optional
Low noise design
Owing to a centrifugal fan and coil, low noise operation is
realized. It is best suited to places where quietness is required.
• Sound pressure level (standard static pressure)
at 15 Pa
Capacity
Sound
High
pressure
Fan
level
Mid
Speed
Low
Demonstrates a maximum external static
pressure of 50 Pa despite its compact
design
P63
External static pressure can be selected from 5, 15, 35 and
1190
50 Pa (set to 15 Pa at the time of factory shipment).
Drain pump
ensures a
lifting height
of up to
550 mm
*This image shows the VMS1 type
(equipped with a drain pump as a standard feature).
P15
P20
P25
P32
P40
28
29
30
32
33
24
25
26
27
30
22
23
24
24
28
dB(A)
P50
P63
35
36
32
33
30
30

Advertisement

loading

This manual is also suitable for:

S seriesWy seriesR2 seriesWr2 series