S-Series
PUMY-SP VKMD-A(-BS)
Model
Power source
Cooling capacity
*1 kW
(Nominal)
*1 Btu/h
Power input
kW
Current input A
COP
kW/kW
Temp. range of
Indoor
W.B.
cooling
Outdoor
D.B.
Heating capacity
*2 kW
*2 Btu/h
(Nominal)
Power input
kW
Current input A
COP
kW/kW
Temp. range of
Indoor
D.B.
heating
Outdoor
W.B.
Indoor unit
Total capacity
connectable
Model/
CITY MULTI
Quantity
Branch box
Mixed
system
Sound pressure level
dB <A>
(measured in anechoic room)
Refrigerant piping
Liquid pipe
mm (inch)
diameter
Gas pipe
mm (inch)
Fan
Type × Quantity
Airflow rate
m³/min
L/s
cfm
Motor output kW
Compressor
Type × Quantity
Starting method
Motor output kW
External finish
External dimension H × W × D
mm
inch
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type × original charge
Net weight
kg (lb)
Heat exchanger
Defrosting method
Optional parts
Notes:
*1,*2 Nominal conditions
Indoor
27ºC DB/19ºC WB
Cooling
(81ºF DB/66ºF WB)
Heating
20ºC DB(68ºF DB)
*3 10 to 52°C(D.B.): When connecting following models such as PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VLE(R)M, PFFY-P20/25/32VKM, and M series, S series, and P series type indoor unit.
*4 −15 to 52°C(D.B.): When using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor unit listed in *3.
*5 94 (207), for PUMY-SP80/112/125/140VKMD-A-BS.
*Nominal conditions *1,*2 are subject to ISO 15042.
*Due to continuing improvement, above specifications may be subject to change without notice.
PUMY-SP80VKMD-A(-BS)
1-phase 220-230-240 V, 50 Hz;
1-phase 220 V, 60 Hz
9.0
30,700
2.11
9.79-9.36-8.97
4.27
15 to 24°C (59 to 75°F)
-5 to 52°C *3,*4 (23 to 126°F) -5 to 52°C *3,*4 (23 to 126°F) -5 to 52°C *3,*4 (23 to 126°F) -5 to 52°C *3,*4 (23 to 126°F)
10.0
34,100
2.27
10.53-10.07-9.65
4.41
15 to 27°C (59 to 81°F)
-20 to 15°C (-4 to 59°F)
50 to 130% of
outdoor unit capacity
P10-P100/9
P22-P80/5
Branch box
CITY MULTI P10-P100
5
1 unit
Branch box P22-P100
2
Branch box
CITY MULTI P10-P100
3
2 units
Branch box P22-P100
3
51/54
9.52 (3/8) Flare
15.88 (5/8) Flare
Propeller Fan × 1
75/75
1250/1250
2649/2649
0.20 × 1
Twin rotary hermetic
compressor × 1
Inverter
2.1
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
981 × 1,050 × 330 (+25)
38-5/8 × 41-3/8 × 13 (+1)
High pressure Switch
Overcurrent detection, Overheat
detection(Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage
protection
R410A × 3.5 kg (8 lb)
93 (205)*5
Cross Fin and Copper tube Cross Fin and Copper tube Cross Fin and Copper tube Cross Fin and Copper tube
Reversed refrigerant circuit Reversed refrigerant circuit Reversed refrigerant circuit Reversed refrigerant circuit
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Outdoor
35ºC DB(95ºF DB)
7ºC DB/6ºC WB(45ºF DB/43ºF WB)
PUMY-SP112VKMD-A(-BS)
PUMY-SP125VKMD-A(-BS)
1-phase 220-230-240 V, 50 Hz;
1-phase 220-230-240 V, 50 Hz;
1-phase 220 V, 60 Hz
12.5
42,700
3.10
14.38-13.75-13.18
4.03
15 to 24°C (59 to 75°F)
15 to 24°C (59 to 75°F)
14.0
47,800
3.17
14.70-14.06-13.48
4.42
15 to 27°C (59 to 81°F)
15 to 27°C (59 to 81°F)
-20 to 15°C (-4 to 59°F)
-20 to 15°C (-4 to 59°F)
50 to 130% of
outdoor unit capacity
outdoor unit capacity
P10-P140/12
P22-P100/7
4
2
P10-P140
5
4
3
4
P22-P100
4
5
2
P10-P140
3
2
P10-P140
4
P22-P100
5
6
P22-P100
52/54
9.52 (3/8) Flare
15.88 (5/8) Flare
Propeller Fan × 1
77/75
1283/1250
2719/2649
0.20 × 1
Twin rotary hermetic
Twin rotary hermetic
compressor × 1
Inverter
3.1
Galvanized Steel Sheet
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
Munsell No. 3Y 7.8/1.1
981 × 1,050 × 330 (+25)
981 × 1,050 × 330 (+25)
38-5/8 × 41-3/8 × 13 (+1)
38-5/8 × 41-3/8 × 13 (+1)
High pressure Switch
High pressure Switch
Overcurrent detection, Overheat
Overcurrent detection, Overheat
detection(Heat sink thermistor)
detection(Heat sink thermistor)
Compressor thermistor,
Compressor thermistor,
Overcurrent detection
Overcurrent detection
Overheating, Voltage
Overheating, Voltage
protection
R410A × 3.5 kg (8 lb)
R410A × 3.5 kg (8 lb)
93 (205)*5
Joint: CMY-Y62-G-E
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Header: CMY-Y64/68-G-E
Pipe length
Level diff erence
7.5m (24-9/16ft.)
0m (0ft.)
7.5m (24-9/16ft.)
0m (0ft.)
SPECIFICATIONS
PUMY-SP140VKMD-A(-BS)
1-phase 220-230-240 V, 50 Hz;
1-phase 220 V, 60 Hz
1-phase 220 V, 60 Hz
14.0
15.5
47,800
52,900
3.84
4.38
17.81-17.04-16.33
20.32-19.43-18.62
3.65
3.54
15 to 24°C (59 to 75°F)
16.0
16.5
54,600
56,300
3.90
4.02
18.09-17.30-16.58
18.65-17.83-17.09
4.10
4.10
15 to 27°C (59 to 81°F)
-20 to 15°C (-4 to 59°F)
50 to 130% of
50 to 130% of
outdoor unit capacity
P10-P140/12
P10-P140/12
P22-P100/8
P22-P100/8
P10-P140/5
P10-P140/5
P22-P100/5
P22-P100/5
3
2
P10-P140
3
6
7
P22-P100
7
53/56
54/56
9.52 (3/8) Flare
9.52 (3/8) Flare
15.88 (5/8) Flare
15.88 (5/8) Flare
Propeller Fan × 1
Propeller Fan × 1
81/83
81/83
1350/1383
1350/1383
2861/2931
2861/2931
0.20 × 1
0.20 × 1
Twin rotary hermetic
compressor × 1
compressor × 1
Inverter
Inverter
3.5
3.7
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
981 × 1,050 × 330 (+25)
38-5/8 × 41-3/8 × 13 (+1)
High pressure Switch
Overcurrent detection, Overheat
detection(Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage
protection
protection
R410A × 3.5 kg (8 lb)
93 (205)*5
93 (205)*5
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
97
2
8