SPECIFICATIONS
222
HEX unit
Solenoid valve is not installed
PWFY-EP100VM-E1-AU
Model
Power source
Heating capacity (Nominal)
Temp. range of heating
Cooling capacity (Nominal)
Temp. range of cooling
Connectable outdoor unit/
heat source unit
Sound pressure level (measured in anechoic room)
Diameter of refrigerant pipe
Diameter of water pipe
Field drain pipe size
External finish
External dimension H × W × D
Net weight
Circulating water
Design pressure
Drawing
Standard attachment
Optional parts
Remark
Note:
*1Nominal heating conditions (PWFY conditions are indicated in the parentheses. )
<Y/R2-Series>
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
(Inlet water Temp. 30°C (87°F), Water flow rate 4.30m
*2Nominal cooling conditions (PWFY conditions are indicated in the parentheses. )
<Y/R2-Series>
Outdoor Temp. : 35°CDB (95°FDB)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
(Inlet water Temp. 23°C (73°F), Water flow rate 3.86m
* Due to continuing improvement, the above specifications may be subject to change without notice.
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C (32°F) or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use ground water and well water.
* Install the outdoor unit (R2-Series) in an environment where the wet bulb Temp. will not exceed 32°C (90°F).
* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
kW
*1
kcal / h
*1
BTU / h
*1
Power input
kW
Current input
A
Outdoor temp.
W.B.
for outdoor unit
W.B.
Inlet Water temp.
-
for heat source unit
-
Inlet Water temp. for PWFY
-
kW
*2
kcal / h
*2
BTU / h
*2
Power input
kW
Current input
A
Outdoor temp.
D.B.
for outdoor unit
D.B.
Inlet Water temp.
-
for heat source unit
-
Inlet Water temp. for PWFY
-
Total capacity
Model / Quantity
dB <A>
mm (in.)
Liquid
Gas
mm (in.)
mm (in.)
Inlet
mm (in.)
Outlet
mm (in.)
mm
in.
kg (lbs)
m
/ h
Operation Volume Range
3
MPa
R410A
MPa
Water
External
Wiring
Document
Accessory
<WY/WR2-Series>
Inlet water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
/h)
(Inlet water Temp. for PWFY side 30°C (87°F), Water flow rate 4.30m
3
<WY/WR2-Series>
Inlet water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
/h)
(Inlet water Temp. for PWFY side 23°C (73°F), Water flow rate 3.86m
3
PWFY-EP100VM-E1-AU
1 - phase 220 - 230 - 240V 50 / 60Hz
0.068 - 0.065 - 0.063
-20 ~ 32°C (-4 ~ 90°F) R2-Series
-20 ~ 15.5°C (-4 ~ 60°F) Y-Series
10 ~ 45°C (50 ~ 113°F) WR2-Series
10 ~ 45°C (50 ~ 113°F) WY-Series
10 ~ 40°C (50~104°F) R2/Y/WR2/WY-Series
0.068 - 0.065 - 0.063
-5 ~ 46°C (23 ~ 115°F) R2-Series
-5 ~ 46°C (23 ~ 115°F) Y-Series
10 ~ 45°C (50 ~ 113°F) WR2-Series
10 ~ 45°C (50 ~ 113°F) WY-Series
10 ~ 35°C (50 ~ 95°F)
50~100% of outdoor/heat source unit capacity
PUHY-P•Y(S)NW-A1(-BS), PUHY-EP•Y(S)NW-A1(-BS),
PQHY-P•Y(S)LM-A1, PURY-(E)P•Y(S)NW-A1(-BS), PQRY-P•Y(S)LM-A1
ø9.52 (ø3/8") Brazed
ø15.88 (ø5/8") Brazed
R1 (R3/4 without expansion joint)
Rc1 (Rc3/4 without expansion joint)
800 (785 without legs) × 450 × 300
31-1/2" (30-15/16" without legs) × 17-3/4" × 11-13/16"
Installation Manual, Instruction Book
Strainer, Heat insulation material, Expansion joint, Flow switch × 1 set, Buffer material
Solenoid valve kit: PAC-SV01PW-E
Details on foundation work, duct work, insulation work, electrical wiring, power source
switch, and other items shall be referred to the Installation Manual.
12.5
10,800
42,700
0.015
11.2
9,600
38,200
0.015
29
ø32 (1-1/4")
NO
33 (73)
1.8 ~ 4.30
4.15
1.00
WKJ94T340
WKE94C951
Unit converter
BTU / h =kW × 3,412
cfm
=m
/ min × 35.31
3
lbs
=kg / 0.4536
* The specification data is subject
/h)
3
to rounding variation.
/h)
3