• System structure
Building management system
BMS
HUB
BACnet
®
To be connectable with
BACnet
® *1
HUB
HUB
LAN2
LAN1
LAN1: For air conditioning systems
LAN2: For BACnet
LAN2
LAN1
LAN2
LAN1
LAN2
LAN1
• Functions
Item
Controllable number of units
Up to 50 units/50 groups
ON and OFF operation for the air conditioning units and general equipment.
ON/OFF
(PAC-YG66DCA is required to operate general equipment.)
Switches between several operation modes depending on the air conditioning unit.
Air conditioning unit: Cool/Dry/Auto(*)/Fan/Heat
Lossnay unit: Heat Recovery/Bypass/Auto
Operation mode
CAHV, CRHV, Air To Water (PWFY) units: Heating, Heating ECO, Hot Water, Anti-freeze, Cooling(**)
* Auto mode is for CITY MULTI R2 and WR2 Series only.
** Only PWFY
Changes the set temperature.
Temperature setting
* Set temperature range varies depending on the indoor unit model.
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
Models with 3 air flow speed settings: Hi/Mid/Low
Fan speed setting
Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.
Air flow direction setting
Air flow direction angles, 4-angles or 5-angles Swing, Auto (Louver cannot be set)
Schedule operation
Weekly schedule can be set by groups based on daily operation pattern.
Individually prohibits operation of each local remote controller function.
Permit/prohibit local operation
(ON/OFF, Operation mode, Set temperature, Filter sign reset, Air Direction*, Fan Speed*, Timer*)
* This function depends on the model.
Indoor unit intake temperature
Measures the intake temperature of the indoor unit only when the indoor unit is operating.
Error
When an error is occurring on an air conditioning unit, the affected unit and the error code are displayed.
Test run
This operates air conditioning units in test run mode.
Ventilation interlock
The ventilation unit (Lossnay) is able to automatically start its operation when operation of the interlocked indoor unit starts.
By using optional external input/output adapter (PAC-YG10HA-E) you can set and monitor the following:
Input: By level signal: "Batch ON/OFF", "Batch emergency stop"
External input/output
Output: "ON/OFF", "Error/Normal"
Bar Graph: Indoor unit Electric Energy, FAN operation time, Thermo-ON time (TOTAL, Cooling, Heating) can be displayed
Energy Management *1
Line Graph: Outdoor temp., Room temp., Set temp. (Heating, Cooling)
Advanced HVAC Controller (AHC)
The status of AHC can only be monitored.
ME remote controller
The status of sensor on this controller can be monitored.
Smartphone/Tablet
The specified web browser on iOS and Android OS can monitor and operate the AE-200E/AE-50E/EW-50E.
New web design
Revised web screen design for a more user friendly interface.
Initial setting software
The initial setting can be configured without the connection of AE-200E/AE-50E/EW-50E.
Apportionment of power consumption
Apportionment of power consumption can be calculated on AE-200 without TG-2000A. *2
BACnet
communication
ANSI/ASHRAE 135-2010 (ISO16484-5) is supported and approved by the BTL.
®
*1. Energy consumption can also be compared with electrical energy targets.
*2. Even when the number of indoor units is 50 or less, the system must consist of AE-200E and EW-50E/AE-50E.
AE-200E M-NET cannot be used.
PC
Wi-Fi Router
M-NET
AE-200E
®
M-NET
(AE-50E/EW-50E)
(AE-50E/EW-50E)
(AE-50E/EW-50E)
(AE-50E/EW-50E)
(AE-50E/EW-50E)
(AE-50E/EW-50E)
: Each unit
By pulse signal: "Batch ON/OFF", "Enable/disable local remote controller"
hourly, daily, and monthly.
input from PAC-YG63MCA and temp. from AHC.
CENTRALISED REMOTE CONTROLLER
Tablet
Smartphone
M-NET
Group 1
M-NET
Group 3
AHC
CO
Sensor
Humidifier
2
BACnet
is a registered trademark of ASHRAE.
®
*1. Please contact your local distributor regarding support for this feature.
: Each group
: Each block
: Each floor
Description
Group 2
Group 4
Heater
: Collective
: Not available
Operations
Display
203