S-Series
PUMY-P VKM5(-BS)
Model
Power source
Cooling capacity
*1
(Nominal)
*1
Power input
Current input
EER
Temp. range of
Indoor temp.
cooling
Outdoor temp.*3,*4
Heating capacity
*2
(Nominal)
*2
Power input
Current input
COP
Temp. range of
Indoor temp.
heating
Outdoor temp.
Indoor unit
Total capacity
connectable
Model /
CITY MULTI
Quantity
Branch box
Mixed
Branch box
system
1 unit
Branch box
2 units *8
Sound pressure level
*5
(measured in anechoic room)
Sound power level
*5
(measured in anechoic room)
Refrigerant piping Liquid pipe
diameter
Gas pipe
FAN
Type x Quantity
Air flow rate
Motor output
*6 External static press.
Compressor
Type x Quantity
Starting method
Motor output
External finish
External dimension HxWxD
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type x original charge
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Optional parts
Notes:
*1,*2 Nominal conditions
Indoor Outdoor Pipe length Level difference
Indoor
27ºC DB/19ºC WB
Cooling
(81ºF DB/66ºF WB)
Heating
20ºC DB(68ºF DB)
*3 10 to 52ºC D.B. [50 to 126ºF D.B.], when connecting following models: PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VKM, PFFY-P20/25/32VLE(R)M and PEFY-P25/32/40VMA3;
and M-Series, S-Series, and P-Series type indoor unit.
*4 -15 to 52ºC D.B. [5 to 126ºF D.B.], when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor unit listed in*3.
*5 Cooling mode/Heating mode
*6 External static pressure option is available (30 Pa/3.1 mmH2O). To use this option, PAC-SJ71FM-E is needed.
*7 When connecting 7 indoor units via branch box, connectable CITY MULTI indoor units are 3; connecting 8 indoor units via branch box, connectable CITY MULTI indoor units are 2.
*8 At least two indoor unit must be connected when using branch box.
*Nominal condition *1,*2 are subject to ISO 15042.
*Due to continuing improvement, above specification may be subject to change without notice.
PUMY-P112VKM5 (-BS)
1-phase 220-230-240V 50Hz,
220-230V 60Hz
kW
12.5
BTU / h
42,650
kW
2.79
A
12.87-12.32-11.80, 12.87-12.32
kW / kW
4.48
W.B.
15.0~24.0°C(59~75°F)
D.B.
-5.0~52.0°C(23~126°F)
kW
14.0
BTU / h
47,768
kW
3.04
A
14.03-13.42-12.86, 14.03-13.42
kW / kW
4.61
D.B.
15.0~27.0°C(59~81°F)
W.B.
-20.0~15.0°C(-4~59°F)
50~130 % of outdoor unit capacity
P10-P140/9
*8
P15-P100/8
CITY MULTI
P15-P140/5
*8
Branch box
P15-P100/5
CITY MULTI
P15-P140/3 or 2 *7
Branch box
P15-P100/7 or 8 *7
dB <A>
49/51
dB <A>
69/71
mm (in.)
9.52(3/8)
mm (in.)
15.88(5/8)
Propeller Fan x 2
m
/min
110
3
L/s
1,833
cfm
3,884
kW
0.074 + 0.074
0
Scroll hermetic compressor x 1
Inverter
kW
2.9
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
mm
1,338 x 1,050 x 330 (+40)
in.
52-11/16 x 41-11/32 x 13 (+1-9/16)
High pressure Switch
Overcurrent detection,
Overheat detection (Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage protection,
Overcurrent detection
R410A 4.8kg
kg (lbs)
123(271)
Cross Fin and Copper tube
HIC circuit
Reversed refrigerant circuit
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Fan motor: PAC-SJ71FM-E
Air protect guide: PAC-SH95AG-E
Outdoor
35ºC DB(95ºF DB)
7ºC DB/6ºC WB(45ºF DB/43ºF WB)
PUMY-P125VKM5 (-BS)
1-phase 220-230-240V 50Hz,
220-230V 60Hz
14.0
47,768
3.46
15.97-15.27-14.64, 15.97-15.27
4.05
15.0~24.0°C(59~75°F)
-5.0~52.0°C(23~126°F)
16.0
54,592
3.74
17.26-16.51-15.82, 17.26-16.51
4.28
15.0~27.0°C(59~81°F)
-20.0~15.0°C(-4~59°F)
50~130 % of outdoor unit capacity
P10-P140/10
P15-P100/8
P15-P140/5
P15-P100/5
P15-P140/3
P15-P100/8
50/52
70/72
9.52(3/8)
15.88(5/8)
Propeller Fan x 2
110
1,833
3,884
0.074 + 0.074
0
Scroll hermetic compressor x 1
Inverter
3.5
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
1,338 x 1,050 x 330 (+40)
52-11/16 x 41-11/32 x 13 (+1-9/16)
High pressure Switch
Overcurrent detection,
Overheat detection (Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage protection,
Overcurrent detection
R410A 4.8kg
123(271)
Cross Fin and Copper tube
HIC circuit
Reversed refrigerant circuit
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Fan motor: PAC-SJ71FM-E
Air protect guide: PAC-SH95AG-E
Pipe length
Level difference
7.5m (24-9/16ft.)
0m (0ft.)
7.5m (24-9/16ft.)
0m (0ft.)
SPECIFICATIONS
PUMY-P140VKM5 (-BS)
1-phase 220-230-240V 50Hz,
220-230V 60Hz
15.5
52,886
4.52
20.86-19.95-19.12, 20.86-19.95
3.43
15.0~24.0°C(59~75°F)
-5.0~52.0°C(23~126°F)
18.0
61,416
4.47
20.63-19.73-18.91, 20.63-19.73
4.03
15.0~27.0°C(59~81°F)
-20.0~15.0°C(-4~59°F)
50~130 % of outdoor unit capacity
P10-P140/12
P15-P100/8
P15-P140/5
P15-P100/5
P15-P140/3
P15-P100/8
51/53
71/73
9.52(3/8)
15.88(5/8)
Propeller Fan x 2
110
1,833
3,884
0.074 + 0.074
0
Scroll hermetic compressor x 1
Inverter
3.9
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
1,338 x 1,050 x 330 (+40)
52-11/16 x 41-11/32 x 13 (+1-9/16)
High pressure Switch
Overcurrent detection,
Overheat detection (Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage protection,
Overcurrent detection
R410A 4.8kg
123(271)
Cross Fin and Copper tube
HIC circuit
Reversed refrigerant circuit
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Fan motor: PAC-SJ71FM-E
Air protect guide: PAC-SH95AG-E
99