S
-Series
Cooling or Heating
• Features ∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
• Optional parts ∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙∙
• Specifications
PUMY-SP VKMD-A (-BS)/YKMD-A (-BS)∙∙∙∙∙∙∙∙
1-fan type
PUMY-P VKM5 (-BS)/YKM4 (-BS)/YKMD-A (-BS)∙∙∙∙∙∙∙
2-fan type
Cooling/heating changeover system with horizontal airflow for
small offices and stores
The CITY MULTI S-Series (for small applications) makes use of a two-pipe refrigerant system, which allows for system
changeover from cooling to heating, ensuring that a constant indoor climate is maintained in all zones. The compact
outdoor unit utilizes R410A refrigerant and an inverter-driven compressor for effective energy use.
With a wide lineup of indoor units connected to a flexible piping system, the CITY MULTI Series can be configured to suit
diverse applications. Thanks to the individual operation of up to 12 units* and a group change function, the CITY MULTI
S-Series can flexibly accommodate layout changes in stores and offices.
• Small offices
• System Pipe Lengths
[SP80~140(VKMD-A/YKMD-A)]
Refrigerant Piping Lengths
Maximum meters [Feet]
Total length
120 [394]
Furthest indoor from outdoor
70 (90 equivalent) [230 (295)]
Furthest indoor from first branch
50 [164] *4
Vertical differentials between units
Maximum meters [Feet]
Indoor/outdoor (outdoor higher)
50 [164]
Indoor/outdoor (outdoor lower)
30 [98]
Indoor/indoor
15 [49]
[P112~140(VKM5/YKM4)]
Refrigerant Piping Lengths
Maximum meters [Feet]
Total length
300 [984]
Furthest indoor from outdoor
150 (175 equivalent) [492(574)]
Furthest indoor from first branch
30 [98]
Vertical differentials between units
Maximum meters [Feet]
Indoor/outdoor (outdoor higher)
50 [164]
Indoor/outdoor (outdoor lower)
40 [131] *3
Indoor/indoor
15 [49]
[P200YKMD-A]
Refrigerant Piping Lengths
Maximum meters [Feet]
Total length
150 [492]
Furthest indoor from outdoor
80 (90 equivalent) [262(295)]
Furthest indoor from first branch
30 [98]
Vertical differentials between units
Maximum meters [Feet]
Indoor/outdoor (outdoor higher)
50 [164]
Indoor/outdoor (outdoor lower)
40 [131]
Indoor/indoor
15 [49]
*1 When the outdoor unit is installed below the indoor unit, top-bottom differential is 30m [98ft].
*2 When the outdoor unit is installed below the indoor unit, top-bottom differential is 40m [131ft].
*3 30m [98ft] or less if PKFY-P*VLM, PFFY-P*VKM, PFFY-P*VL* type of indoor units are included.
*4 Use liquid pipe of ø9.52 for less than P50 indoor units, when farthest length from the first joint exceeds 30 m.
Heat pump
P.92 - P.96
P.94
P.97 - P.98
P.99 - P.100
Outdoor unit
Outdoor unit
Furthest indoor from outdoor
90m [295ft]
Top-bottom
(equivalent length)
differential
(actual length 70m [230ft])
50m [164ft] *1
Between indoor units
top-bottom differential
15m [49ft]
Indoor
unit
Outdoor unit
Furthest indoor from outdoor
175m [574ft]
Top-bottom
(equivalent length)
differential
(actual length 150m [492ft])
50m [164ft] *2 *3
Between indoor units
top-bottom differential
15m [49ft]
Indoor
unit
Outdoor unit
Furthest indoor from outdoor
90m [295ft]
Top-bottom
(equivalent length)
differential
(actual length 80m [262ft])
50m [164ft] *2
Between indoor units
top-bottom differential
15m [49ft]
Indoor
unit
91
*For P140 and P200 models