Mitsubishi Electric MELSEC-Q Structured Programming Manual page 269

Hide thumbs Also See for MELSEC-Q:
Table of Contents

Advertisement

FXCPU Structured Programming Manual
[Device & Common]
PLC
Error
operation
code
at error
occurrence
Syntax error [M8065(D8065)]
0000
-
No error
Incorrect combination among instruction, device
6501
symbol and device number
"OUT T" or "OUT C" is not provided before the set
6502
value.
The set value is not provided after "OUT T" or
6503
"OUT C".
Stops
Insufficient number of operands in an instruction
operation
A same label number is used more than once.
6504
A same interrupt input or high speed counter input
is used more than once.
6505
The device number is beyond the allowable range.
6509
Other error
Circuit error [M8066(D8066)]
0000
-
No error
The LD or LDI instruction is used continuously 9
6601
times or more.
The LD or LDI instruction is not provided.
A coil is not provided.
The relationship between LD/LDI and ANB/ORB
is improper.
6602
The STL, RET, MCR, EI, DI, SRET, IRET, FOR,
NEXT, FEND or END instruction, P (pointer) or I
(interrupt) is not connected to the bus line.
The MPP instruction is not provided.
The MPS instruction is used continuously 12 times or
6603
more.
The relationship among MPS, MRD and MPP
6604
instructions is improper.
The STL instruction is used continuously 9 times
or more.
The MC, MCR, I (interrupt) or SRET instruction is
6605
provided inside the STL instruction.
The RET instruction is provided outside STL
instruction.
Stops
The RET instruction is not provided.
operation
P (pointer) or I (interrupt) are not provided.
SRET or IRET instruction is not provided.
I (interrupt), SRET or IRET instruction is provided
6606
in the main program.
The STL, RET, MC or MCR instruction is provided
in a subroutine or interrupt routine.
The relationship between the FOR instruction and
the NEXT instruction is improper.
The nesting level between the FOR instruction
6607
and the NEXT instruction is 6 or more.
The STL, RET, MC, MCR, IRET, SRET, FEND or
END instruction is provided between the FOR
instruction and the NEXT instruction.
The relationship between the MC instruction and
the MCR instruction is improper.
MCR NO is not provided.
6608
The SRET or IRET instruction or I (interrupt) is
provided between the MC instruction and the
MCR instruction.
6609
Other error
Contents of error
5.3 FX0S/FX0/FX0N/FXU/FX2C PLCs
Action
Each instruction is checked during programming.
If a syntax error occurs, correct the improper instruction in the
program mode.
This error occurs when a combination of instructions is incorrect in
the entire circuit block or when the relationship between a pair of
instructions is incorrect.
Correct the instructions in the program mode so that their mutual
relationship becomes correct.