SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
Series
User Manual
Alarm
Alarm Name
ID
2036
Grid
Overfrequency
2037
Grid
Underfrequenc
y
Issue 07 (2021-07-08)
Alarm
Cause
Severity
Major
Cause ID=1
Power grid exception: The
actual power grid
frequency is higher than
the standard requirement
for the local power grid.
Major
Cause ID=1
Power grid exception: The
actual power grid
frequency is lower than
the standard requirement
for the local power grid.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Troubleshooting Suggestions
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid frequency is
within the acceptable
range. If not, contact the
local power operator. If yes,
modify the grid
overfrequency protection
threshold through the
mobile app, SmartLogger,
or NMS with the consent of
the local power operator.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid frequency is
within the acceptable
range. If not, contact the
local power operator. If yes,
modify the grid
underfrequency protection
threshold through the
mobile app, SmartLogger,
or NMS with the consent of
the local power operator.
96