4.4
Basic System
4.4.1 System Summary
Design Example 1 Basic system
Lossnay
Non-polar
2 wires
Power supply
Remote controller
PZ-41SLB-E
This is a simple system.
A Lossnay is operated independently
with 1 remote controller.
4.4.2 Operation of Multiple Units
For LGH-50/100RX types, 1 remote controller can operate from 1 to 15 Lossnay units. For using LGH-
Feature
200RX type, 1 remote controller can operate from 1 to 7 Lossnay units.
Remote controller
Ordered part
PZ-41SLB-E
• Also connect the power to the second and following Lossnay units.
• The maximum extension of the transmission cable is 500 m or less (between Lossnay and remote
Notes
• The main or Sub setting on the Lossnay is necessary.
Note:
The external device operation signal, and pulse signals can only be connected to the Lossnay on the "Main" setting.
When the M-NET system is connected, do not connect the transmission cable to TM2.
System Example
controller switch, between Lossnay and Lossnay).
Lossnay
(Main)
Power supply
(Transmission cable
extension is 500 m or less)
PVC cable ø0.65 to 1.2 or
strand wire 0.3 mm
Remote controller
PZ-41SLB-E
Design Example 2 Lossnay control of multiple units
Non-polar
2 wires
Remote
controller
PZ-41SLB-E
Design Example 3 2 remote controller system
Non-polar
2 wires
Remote controller
PZ-41SLB-E
Lossnay
(Sub)
up to
15 units
Power supply
(Be sure to turn on the
power for the second and
2
2
to 1.25 mm
.
following Lossnay units.)
Up to 15 Lossnay units can be
controlled at one time with 1
Lossnay
remote controller switch.
(Main)
(up to 7 units when using LGH-
200RX type)
Power supply
Lossnay
(Sub)
Power supply
The Lossnay can be controlled
from 2 remote locations.
The remote controller gives pri-
Lossnay
ority to the last touch.
Power supply
Lossnay
(Sub)
Power supply
115